Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 61 © Saftronics, Inc.
§ MEMOBUS Frequency Reference Unit (n105)
The frequency reference units from the PLC and in the frequency reference and output frequency monitors (by
communication) are selected. The output frequency resolution of the FP5/GP5 is 0.1 Hz. Even if the frequency
reference unit is changed to 0.01 Hz in constant n105, the value in the hundredth digit of 0.01 Hz of the received
frequency reference is rounded off internally. When 30000/100% in units of 0.1% is selected, the value is rounded
off in the same way.
§ MEMOBUS Slave Address (n106)
The slave address number is set. It is necessary to set the address number so that it will not overlap with the
address number of another slave connected on the same transmission line.
NOTE: To change the values set in constants n106 to n108 and enable new settings, it is necessary to turn OFF the power supply, and
then turn it ON again.